POWER GENERATION

Model CIPR – 25Z

Model CIPR – 25Z

IAQH-1000 · 1 MBTU/h indirect-fired heater

One-million-BTU indirect-fired heater with a 26:1 modulating burner and 16,000 CFM of clean, dry air — for curing and drying on enclosed jobsites.

60 Hertz — Frequency

3 — Phase

2375 lbs — Weight

Features
• Prototype & Production Tested Design Alternator
• Wide range of options and accessories available • Clean power with the Mecc Alte ECP28-VL
• Simple access for maintenance and operations • Regulator provides 0.5% voltage regulation
• Weatherproof enclosure with 110% fluid containment • High efficiency alternator
• Safety guards for all electrical connections and moving parts Engine
• Lockable latches standard with key or external lock • Heavy duty Kubota WG2503 engine
• Engineered vibration dampening system • E Controls Fuel System
• Single point lifting bail system, engineered and rated • Environment Canada / US EPA emissions compliance
• Rugged base frame and enclosure for mobile applications • Integral mechanical fan system optional electrical cooling system
• Internal silencer and catalytic converters • Complete with engine fluids, ready for operation
• All parts powder coated or galvanized Controls
• Murphy low oil protection standard on all models • Standard controls: DEIF SGC 120
• Power distribution system is customizable Eco Glands • Emergency stop externally accessible
• Optional long run oil tank options • Remote cellular or satellite telematic ready
• Display of all critical genset measures • Fully programmable controller for application integration
Specifications
Manufacturer Kubota
Model WG2503
Stroke 4
Fuel Natural Gas or Vapour Propane
Emissions Compliance Enviroment Canada / US EPA
Number and disposition of cylinders I4, Inline
Total Displacement 2491 cc
Air Intake Naturally Aspirated
Starting System Electric – 12V
Speed / Speed Governor 1800 RPM
Lube Oil Capacity 7.5 L / 2.0 GAL
Oil Type (See chart based on ambient operating temps in manual) API SL or higher SAE10W-30
Engine Cooling Fan System Mechanical
Coolant Capacity
Fuel Guidelines Propane HD5; ≥ 90% PROPANE (C3H8), ≤ 5% (C3H6), ≤ 5% OTHER
Utility Natural Gas ≥ 75 MN, ≥ 50% (CH4), 950-1120 BTU/SCF (HHV)
Well Head Gas: ≥ 75 MN, ≥ 70% (CH4), 700-2362 BTU/SCF (LHV)
Engine

(Reference Power conditions are ISO 8528, barometric pressure 100 kPa, temperature 25°C, humidity 30%.)

Compliance / Approvals ETL
Natural Gas Propane
Power Amps @ 0.8 PF Power Amps @ 0.8 PF
Standby Power 31  kVA

23  kW

80  @ 208, 3Ø

120  @ 240, 1Ø

33  kVA

26  kW

90  @ 208, 3Ø

135  @ 240, 1Ø

Prime Power 29  kVA

20  kW

69  @ 208, 3Ø

104  @ 240, 1Ø

30  kVA

24  kW

83  @ 208, 3Ø

125  @ 240, 1Ø

Weight 2375  lbs 1079.5  kgs
Frequency 60  Hertz
Phase 3  Phase
Power Factor 0.8  Cosφ

Power Distribution (Standard)
• 4 x 120v GFCI, 20 Amp Duplex
• 2 x 125/250v 30 Amp twistlock
• 2 x 125/250v 50 amp twistlock
• Hard Wire Lugs with shunt trip controlled door
Dimensions: 43.67 L x 74.5 W x 49.5 H
Voltages: 120/208, 120/240, 220/380, 277/480, 400, 347/600
Cellular or satellite telematic system integration
LPG liquid vaporizer kit